GROWATT Grid-connect Commercial PV Inverter 30kW - 40kW | MID30KTL3-X-AU - MID40KTL3-X-AU

1 Ratings
Type Three-phase
Power Range 45kW - 60kW
Region China


Model No.
MID 30KTL3-X-AU MID 33KTL3-X-AU MID 36KTL3-X-AU MID 40KTL3-X-AU
Warranty
Product Warranty 10-year Product Warranty on Materials and Workmanship
Input side (DC)
Maximum DC input power for each MPPT (Pmpptmax)
45,000W 49,500W 54,000W 60,000W
Absolute maximum DC input voltage (Vmax)
1100V 1100V 1100V 1100V
Rated DC input voltage (Vdcr)
600V 600V 600V 600V
Start-up DC input voltage (Vstart)
250V 250V 250V 250V
Maximum DC input current (Idcmax)
32A 32A 32A 32A
MPPT input DC voltage range
200-1000V 200-1000V 200-1000V 200-1000V
Number of independent MPPT
3 3 4 4
Rated DC input power (Pdcr)
600V 600V 600V 600V
Output side (AC)
Rated AC power
30,000W 33,000W 36,000W 40,000W
AC voltage range
220V - 440V 230V - 400V 340V - 440V 340V - 440V
Nominal AC voltage
220V 230V 230V 230V
Rated AC grid voltage
220V 230V 230V 230V
Maximum AC output current
45.5A 50.0A 54.5A 60.6A
Output frequency range
45 - 65 Hz 45 - 65 Hz 45 - 65 Hz 45 - 65 Hz
Rated output frequency
50/60 Hz 50/60 Hz 50/65 Hz 50/65 Hz
Nominal power factor and adjustable range
0.8Leading ...0.8Lagging 0.8Leading ...0.8Lagging 0.8Leading ...0.8Lagging 0.8Leading ...0.8Lagging
No. of Feed-in Phase
3W+N+PE 3W+N+PE 3W+N+PE 3W+N+PE
Maximum efficiency
98.80% 98.80% 98.80% 98.80%
Weighted efficiency (EURO/CEC)
98.50% 98.50% 98.50% 98.50%
General Data
Dimensions (H/W/D)
580 x 435 x 230mm 580 x 435 x 230mm 580 x 435 x 230mm 580 x 435 x 230mm
Weight
30kg 30kg 30kg 30kg
Power Consumption as night
1W 1W 1W 1W
Operating Temperature –25°C ... +60°C (>45°CDerating)
Protection Class IP66
Transformer Transformerless
Humidity 0~100%
Interface OLED + LED
Protection Features DC reverse-polarity protection,DC switch,DC Surge protection,Insulation resistance monitoring,AC surge protection,AC short-circuit protection,Ground fault monitoring,Grid monitoring,Anti-islanding protection,Residual-current monitoring unit,String monitoring,AFCI protection
PDF image