1 Ratings
Type Three-phase
Power Range 20kW - 27.6kW
Region Italy


Model No.
TRIO-20.0-TL-OUTD TRIO-27.6-TL-OUTD
Warranty
Product Warranty 10-year Product Warranty on Materials and Workmanship
Input side (DC)
Maximum DC input power for each MPPT (Pmpptmax)
12000W 16000W
Absolute maximum DC input voltage (Vmax)
1000V 1000V
Rated DC input voltage (Vdcr)
620V 620V
Start-up DC input voltage (Vstart)
430V (adj. 250V - 500V) 430V (adj. 250V - 500V)
Maximum DC input current (Idcmax)
50 A 64 A
MPPT input DC voltage range
440V - 800V 440V - 800V
Number of independent MPPT
2 2
Rated DC input power (Pdcr)
20750W 28600W
Output side (AC)
Rated AC power
20000W 27600W
AC voltage range
320V - 480V 320V - 480V
Rated AC grid voltage
400V 400V
Maximum AC output current
33 A 45 A
Output frequency range
47 Hz - 53 Hz 57 Hz - 63 Hz
Rated output frequency
50 Hz 60 Hz
Nominal power factor and adjustable range
> 0.995 > 0.995
Maximum efficiency
98.2% 98.2%
Weighted efficiency (EURO/CEC)
98% 98%
General Data
Dimensions (H/W/D)
1061 x 702 x 292 mm (41.7” x 27.6” x 11.5”) 1061 x 702 x 292 mm (41.7” x 27.6” x 11.5”)
Weight
< 70.0 kg / 154.3 lbs (Standard version) < 75.0 kg / 165.4 lbs (Standard version)
Power Consumption as night
< 0.6 W < 0.6 W
Noise Level
50 dBA @ 1 m 50 dBA @ 1 m
Operating Temperature -25°C to +60°C
Protection Class IP 65 rated
Transformer Transformerless
Humidity 0% to 100% condensing
Interface Graphic display, PVI-USB-RS232_485 (optional)
Protection Features Reverse polarity protection,Input over voltage protection for each MPPT,Photovoltaic array isolation control,Anti-islanding protection,Maximum external AC overcurrent protection,Output overvoltage protection